Micro-channel reactor thermostatically controlled air-cooled chiller compressor troubleshooting meth
The air-cooled chiller is a temperature
control device that is widely used in the microchannel reactor industry. Wuxi
Guanya LNEYA has produced a cold and heat source thermostatically controlled
air-cooled chiller for the microchannel reactor industry. If the compressor
fails during operation, it needs to be investigated and solved in time.
To troubleshoot the micro-channel reactor
thermostatically controlled air-cooled chiller compressor, first check the
circuit part to see if the equipment power supply, voltage, and switch are
normal; see if the equipment power supply is powered, the voltage is normal,
and the switch contacts are good , Whether the power supply lacks phase. When
the equipment is not equipped with an ammeter or a voltmeter, a multimeter or a
tester can be used to check the power supply. When the power supply voltage is
too low, the compressor cannot be started.
If the compressor of the micro-channel
reactor thermostatically controlled air-cooled chiller adopts a piston
compressor, whether the big end bearing bush and the curved sleeve of the
connecting rod are caught. These may be caused by the excessively high exhaust
temperature during the previous operation, or it may be caused by the coking of
the lubricating oil, which causes the cylinder and the piston to stick
together, which prevents the compressor from starting.
Check the thermostatically controlled
air-cooled water chiller differential pressure relay and high and low voltage
relay of the microchannel reactor. When the oil pressure of the compressor is
abnormal, the compressor can be stopped. At the same time, when the compressor
discharge pressure and suction pressure are abnormal, neither of them can be
started or the compressor will quickly stop running after it has been started.
Check whether the amount of chilled water, cooling water, and water temperature
are normal. If the water volume is small and the water temperature is high, it
will cause the condensing pressure to rise sharply and the evaporation
temperature to drop rapidly. Due to the action of the unit protection
facilities, the unit often shuts down quickly.
Check whether the solenoid valves and
regulating valves related to the equipment are malfunctioning, and whether they
are opened or closed as required. Check whether there is a leakage of working
fluid in the temperature sensing bag of the temperature relay, or the
adjustment is wrong.
Before use, the corresponding preparations
must be done well in order to run efficiently.
Recomendaciones relacionadas
-
¿Qué tipo de sistema de control de la temperatura se necesita para la preparación de frotis en la industria farmacéutica?
869En la industria farmacéutica, el secado por presión negativa y la preparación de frotis tienen requisitos específicos para el control de la temperatura, y suelen requerir dispositivos de control de temperatura precisos y ajustables para garantizar la calidad del producto y la esta...
Ver detalles -
Introduction of temperature control equipment for cannabis extraction
1047CO2 is a unique solvent because its dissolving power can be changed by simply adjusting the temperature and pressure during the extraction process. When the pressure and temperature of CO2 are higher than 1083 psi and at 88F, CO2 is considered sup...
Ver detalles -
Integrated temperature control unit for reactors in pharmaceutical production
878The reactor system can effectively cooperate with the integrated temperature control system to meet the temperature control requirements of different chemical reactions and production processes. The reactor temperature control equipm...
Ver detalles -
Detailed introduction of the motor control cooling system Chiller
1292With the continuous development of new energy vehicles, the motor control cooling system Chiller is also under continuous development. The new energy vehicle motor test special chiller can adaptively adjust the cooling capacity of the chiller acco...
Ver detalles