1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Recomendaciones relacionadas
-
Reunirse en Shanghai World Expo Pavilion 【Pesticide Exhibition】Booth 1G10 10.12-10.14
1997Nombre de la exposición: La 20ª Conferencia Nacional de Intercambio de Plaguicidas y Salón de Exposición de Productos AgroquímicosHora de la exposición: 12-14 de octubre de 2020Número de stand: 1G10Dirección de la exposición: Shanghai World Expo Exhibition Hall ,
Ver detalles -
How to choose a laboratory deionized water chiller?
2070Pure water usually refers to water that has been treated to remove impurities, ions, organic matter, etc. Common examples include distilled water, reverse osmosis water, and deionized water. Deionized water has low conductivity due to t...
Ver detalles -
Effect Of Humidity On Laboratory Chillers
1577The high humidity reduces the insulation strength of the electrical equipment of the chiller in the laboratory. The moisture in the air adheres to the surface of the insulating material to form condensation, which reduces the insulation resistance...
Ver detalles -
What determines the price of a brand’s refrigeration and heating circulator?
1638The price of the brand's refrigeration and heating circulator is mainly determined by the three major parts of raw materials, manufacturing costs, and technical costs, which affect the subsequent quotation. The composition of the refrigeration he...
Ver detalles
LNEYA Enfriadoras industriales Fabricante Proveedor