Precautions for changing the refrigerating oil in the cooling system of the car charger
The cooling system of the car charger should pay attention to the condition of the refrigerating oil during the operation. After the compressor is started, carefully observe the changes in the oil temperature and oil pressure. If the oil changes color, the oil must be changed until the system is clean. Piston refrigerators that are normally put into production and operation must undergo a limited period of maintenance after long-term operation and replace the refrigerating oil.
1. Refrigerating oil replacement operating procedures
1. Close the high-pressure exhaust and low-pressure suction shut-off valves, and use the process valve needle on the compressor to release the refrigerant inside the compressor to make the crankcase of the compressor communicate with the atmosphere.
2. Unscrew the oil drain plug at the bottom of the crankcase, drain the refrigerant oil in the crankcase, and remove the filter for cleaning.
3. Nitrogen can be blown in from the low-pressure inflation valve needle, and the oil drain port can be blocked by hand to increase the pressure in the body, and further remove the residual oil in the body, dry the cleaned filter into the body and tighten the oil drain plug .
2. Refrigerating oil injection
Plan 1: Unscrew the process port plunger on the side of the compressor crankcase, use it as a filling port to pour the refrigerated oil into the crankcase through a suitable tool;
Option 2: (for piston machine) connect the low-pressure pipe of the fluorine-filling meter to the low-pressure process valve needle of the cavity of the piston-type refrigerator, use a vacuum pump to pump the crankcase to negative pressure, and remove the other fluorine-filling pipe separately, one end Insert it into the container containing the refrigerated oil, and connect the other end to the valve needle of the low-pressure suction end of the oil pump, and suck the refrigerated oil into the crankcase by using the negative pressure in the crankcase.
Summary of considerations:
1. You can add a little less when changing the oil, and generally add it to the lower limit of the sight glass.
2. After the refrigerating oil filling is completed, tighten the process plunger or remove the fluorine filling tube, and connect the fluorine pressure gauge to vacuum the compressor.
3. After the vacuum is completed, open the compressor high and low pressure stop valve to check whether there is refrigerant leakage.
4. After turning on the cooling system, check the compressor lubrication and the oil level of the oil glass immediately. If the oil level is lower than the normal range, add refrigerating oil. If necessary, connect an oil pressure gauge to the needle valve of the oil pump to check the oil pressure.
5. The suction side pressure of the oil pump of the semi-hermetic piston compressor should be basically the same as the low pressure suction pressure, and the allowable value of the oil pressure difference.
Matters needing attention:
The refrigerated oil in the cooling system of the car charger is hygroscopic, and the moisture in the oil chemically reacts with the oil. It requires special care when working to minimize the air entering the system and the oil storage container; the refrigerating oil should not be added in excess. If the refrigerating oil is added in excess, There is a danger of liquid shock when the cooling system is reopened.
Recomendaciones relacionadas
-
Storage tank cooling refrigeration chiller
1412Tank cooling chiller is a device specifically used to cool materials in a tank to ensure that the materials in the tank are stored within a suitable temperature range to maintain the quality and performance of the materials. This type of c...
Ver detalles -
¿Es fiable la unidad de refrigeración de baja temperatura - 120 grados de efecto refrigerante?
1931LNEYA se especializa en la producción de unidades de refrigeración criogénica de un solo fluido, el rango de temperatura de refrigeración es de -150 grados a -5 grados, lo que puede satisfacer diferentes requisitos de temperatura de refrigeración. Los productos son ampliamente utilizados en...
Ver detalles -
About the size and installation height of refrigeration heating temperature control system equipment
1397Whether it is biopharmaceutical, traditional Chinese medicine or chemical pharmacy, pharmaceutical companies are all related to chemistry, because the extraction and synthesis of pharmaceutical ingredients are all in the form of chemical products...
Ver detalles -
Method for connecting reaction kettle and electric control cabinet of reaction equipment
1651The supporting equipment of the reaction kettle is the temperature control product provided by our company for the majority of users for the users. When the user selects the equipment for the reaction kettle, it is necessary to understand the conn...
Ver detalles
LNEYA Enfriadoras industriales Fabricante Proveedor