How to troubleshoot the failure of the material aging test chiller?
Regular maintenance work for the material aging test chiller, and troubleshooting is also very important.
1. Exhaust at double high pressure, heat dissipation may be problematic.
When it is detected that the high and low pressure of the system are higher than normal, it is usually because there is air in the system or excessive refrigerant is added. At this time, it is necessary to re-evacuate and add an appropriate amount of refrigerant to solve the problem. However, there is another situation, that is, poor heat dissipation, especially when the ambient temperature is relatively high, which often leads to worse heat dissipation. The cause of this failure is generally that the heat sink is blocked, dirty, and the speed of the heat dissipation fan is not enough.
2. Refrigerant with low pressure loss, otherwise the system will be blocked.
When the high and low pressures are both low, there are two possibilities:
(1) If the system is blocked, the blocked part will produce throttling, and there will be a significant temperature difference in the throttling part, and the problem can be found by feeling it with your hands.
(2) The leakage of refrigerant leads to insufficient refrigerant. This situation is more common. At this time, the material aging test cooler detector must be used to find out the leaking location and perform replacement.
3. Low pressure, high pressure, low pressure, replace the compressor.
When the material aging test cooler pressure gauge detects that the low pressure is higher than normal, and the high pressure is lower than normal, at this time, it is recommended that the chiller refrigeration cannot achieve the effect of the normal material aging test enfriadora. The reason is likely to be the wear and tear in the material aging test enfriadora pump, resulting in a drop in power. At this time, it is often necessary to replace the compressor to solve the problem.
4. There is water vapor in the meter shake system, so it must be changed when it is timed out.
When the material aging test cooling machine system is working, if the pressure gauge needle keeps shaking, it means that there is moisture in the system. To solve this problem, it is generally necessary to re-evacuate, and the pumping time must be no less than 15 minutes. If necessary, the drying bottle needs to be replaced to drain the water in the system.
Recomendaciones relacionadas
-
Which industries are applicable to semiconductor device testing?
1101Semiconductor device testing is used in many semiconductor industries. So, how much do you know about semiconductors and conductors for semiconductor device testing? The properties of this substance are still recommended to the user. In general, s...
Ver detalles -
Collocation Requirements For Lab Water Chiller
1153The lab water chiller is a relatively advanced cryopreservation equipment, which is suitable for blood stations, hospitals, health and epidemic prevention systems, scientific research institutes, electronic industry, chemical medicine, biological ...
Ver detalles -
Description of operation characteristics of fully enclosed refrigeration and heating machine
1386In the petroleum, chemical, and pharmaceutical industries, fully enclosed refrigeration and heating integrated machines are needed by many enterprises. However, when users choose to make choices, they must understand their operating characteristic...
Ver detalles -
Brief introduction of explosion-proof curve heating and cooling thermostat
963The explosion-proof curve heating and cooling thermostat SUNDI series adopts compressor refrigeration and linkage heating technology, an integrated piping system, and a plate heat exchanger. It is suitable for equipment connecting reactors for ref...
Ver detalles