The Phenomenon of Ice Jam in Low Temperature Chiller System
The phenomenon of ice jam in low temperature chiller system is mainly due to the excessive water in the refrigeration system. With the continuous circulation of refrigerants, the water in the refrigeration system gradually concentrates at the outlet of expansion valve. Because the outlet of expansion valve has the lowest temperature, the water turns into ice and the ice enlarges gradually. To a certain extent, the expansion valve will be completely blocked, resulting that the refrigerant can not be recycled, and the cold storage will not refrigerate.
The phenomenon of ice jam in low temperature sistema de refrigeración is normal in the initial stage. There is frost in the evaporator, heat dissipation of the condenser, stable operation of the unit, clear and stable movement of refrigerant in the evaporator. With the formation of ice jam, the air flow is gradually weakened and intermittent. When the jam becomes serious, the sound of air flow completely disappears. The refrigerant cycle is interrupted. And the condenser is gradually cooled.
Because of the blockage, the exhaust pressure rises. The sound of the machine increases. There is no refrigerant flowing into the evaporator. The frost area decreases gradually. The temperature increases gradually, and the temperature of the expansion valve rises together, so the ice begins to melt. At this time, the refrigerant begins to recycle again. After a period of time, ice blockage occurs again, forming a periodic phenomenon of through-blockage.
Troubleshooting of Ice Block
The ice jam failure of low temperature chiller system is due to excessive moisture in the system, so the whole refrigeration system must be dried. There are two ways to deal with it:
1. Heat and dry the components of the refrigerant system in a drying box. Remove the compressor, condenser, evaporator, expansion valve and return pipe in the refrigerant system from the cold storage and put them into the drying box for heating and drying.
2. Remove the water content of each part of the refrigeration system by heating and secondary vacuum extraction.
Recomendaciones relacionadas
-
Details of the types&functions and characteristics of industrial chillers
1536When it comes to industrial chillers, everyone must know it, but what are the specific types? It is a kind of cooling equipment that can continuously perform the cooling function, which is also an important manifestation of the function of industr...
Ver detalles -
How to solve the frosting phenomenon of 50p freezer compressor?
165150p freezer is used in industrial cold treatment, but if the performance is not good, it may lead to industrial work, especially if it is faulty, it is more difficult to solve. Therefore, it is better to understand the various faults of the 50p re...
Ver detalles -
Do new energy vehicle motor tests require a chiller or heater?
1294New energy vehicle motor testing requires both a chiller and a heater, as motor testing covers a wide range of temperature conditions to ensure the performance and stability of the motor under different operating conditions. Chiller: In ...
Ver detalles -
Vocs condensing separation equipment expansion valve maintenance instructions
1428Once the expansion valve of the vocs condensing and separating device fails, if the solution is not solved in time, the entire vocs condensing and separating device may be unavailable. Therefore, the failure of the expansion valve of the vocs cond...
Ver detalles
LNEYA Enfriadoras industriales Fabricante Proveedor