How to prevent the freezing pressure of the bearing quick freezing box from being too low?
In the refrigeration system of the bearing blast chiller, if the condenser installation is not in the enclosed space, the system’s exhaust pressure (condensation pressure) tends to be lower in winter (or low temperature), which is often more common in the north. For bearing blasters, this is also the case for other equipment.
The low condensing pressure of the bearing quick freezing box will make the expansion valve unable to obtain sufficient pressure drop at both ends, and it is difficult to supply the appropriate refrigerant to the evaporator. On the one hand, the cooling capacity of the refrigeration system will not meet the requirements, and the system will also be made. Frequent low-voltage alarms and other faults.
To this end, we can deal with the method of exhaust pressure controller. When the intermittent operation of the fan is simple and easy to use, and the technology is mature, the controller used is a pressure controller. This pressure controller can control the intermittent start and stop of the fan. When the pressure is too low, turn off the fan. When the pressure is too high, turn on the fan. Generally, on a small-capacity unit, use two or more fans, one of which is normally open, and the other fans are pressure controlled. The controller controls the start or stop of the fan by the level of the condensing pressure.
It is also possible to use a pneumatic control device to utilize a high-pressure refrigerant-driven piston-type damper. This control device can operate as a stable exhaust pressure as the fan speed controller; the main reason is that the inlet pressure of the expansion valve does not resemble a fan. Intermittent operation produces large fluctuations, and the louver device can be installed either at the air inlet or at the air outlet.
In addition, the condenser overflow device can also be used to increase the condensing pressure of the system by using excess refrigerant, and the condenser overflow device is used for warming or low temperature environment, and the large flow refrigerant is taken from the liquid storage device. It is sent to the condenser, and the excess refrigerant is used to increase the condensing pressure of the system, thereby avoiding the failure of the condensing pressure being too low at low temperatures.
LNEYA’s methods to prevent the bearing chiller from condensing too low pressure are still relatively high, and users can try it according to their own needs.
Recomendaciones relacionadas
-
Operating Principle of LNEYA Industrial Air Chillers
1625Industrial air cooler is a heat exchanger which USES air to cool the hot fluid. The hot fluid in the tube is heated through the exchange of heat between the tube wall, the fin and the outside air, which is usually supplied by the ventilator. Our I...
Ver detalles -
Cita en el stand 6002 de Shanghai World Expo Hall【Testing Expo】9.14-9.16
1526Nombre de la exposición: Shanghai International Automobile Testing and Quality Control ExhibitionTiempo de la exposición: Del 14 al 16 de septiembre de 2020Número de stand: 6002Dirección de la exposición: Shanghai World Expo Exhibition Hall, Pabellón 1,
Ver detalles -
Various reactors and materials use PLC temperature control system
1850The PLC temperature control system is used for the lifting and constant temperature control of glass reactors, metal reactors and bioreactors, especially for heat exothermic control in the reaction process. The heat transfer oil in the jacket of t...
Ver detalles -
Aplicación del compresor en refrigeradores de baja temperatura
1589Compressor is an important part of cryogenic refrigeration industry. As far as low temperature chiller is concerned, different brands and types need to be selected when buying compressors. Therefore, when choosing cryogenic refrigeration compresso...
Ver detalles
LNEYA Enfriadoras industriales Fabricante Proveedor