What are the common debugging problems in low temperature refrigeration baths?
When the low-temperature cooling bath is in debugging, if the local cooling effect is not good, the system may be blocked by foreign matter or the system design is unreasonable and cannot be adjusted normally. At this time, LNEYA removes foreign matter and thoroughly cleans it to adjust the slope of the pipeline.
When debugging, it is found that the vibration and noise of the pump are large when it is running. It may be that the axial and radial deviation of the coupling is large. It may be that the pump flange is too large and the anchor bolts are unevenly stressed. It is the natural vibration frequency of the pump and the pipeline that cause resonance. At this time, the axial and radial deviation of the coupling are adjusted quickly. Adjust the natural vibration frequency between the pump and the pipe, install the relevant soft joint parts, replace the flange and make the anchor bolts evenly.
During commissioning, it was found that the cooling capacity could not reach the required fixed value. It may be that the cooling tower water temperature did not reach the specified cooling parameter, or the pump output was insufficient, or the condenser isolation gasket was misplaced and could not be cooled, or the pipeline in the condenser was blocked. Repair the cooling tower to meet the water temperature and water requirements, remove foreign matter in the pipeline, and check if the condenser isolation gasket is misaligned.

If the exhaust pressure is too high, it is necessary to pay attention to whether the cooling water is insufficient, whether the condensation in the condenser heat transfer tube is serious, whether the cooling water temperature is too high, whether there is too much air in the system, check the cause, repair the cooling tower, and heat transfer of the condenser. The tube is cleaned to remove air from the system.
If severe frost formation is found, check if the return air filter is clogged, if the exhaust air volume is loose after the fan belt is loose, and if the return air valve is too small, it is recommended to clean the return air filter and adjust the fan belt. Adjust the size of the return air valve.
Common faults encountered in the commissioning of these low-temperature refrigeration baths, we try to check them before debugging, try to avoid these faults.
Recomendaciones relacionadas
-
¿Cómo limpiar el sistema de control del aire?
1254In order to respond to the requirements of the two types of society in the country, environmental protection and conservation have become increasingly important. Therefore, in order to extend the life of the product, it is still necessary to have ...
Ver detalles -
Proceso de reparación de averías en compresores de máquinas de ciclo cerrado frío y caliente
966LNEYA's closed-type hot and cold cycle machine adopts single-machine self-cascading refrigeration technology, and its compressor also uses the brand compressor, which is more stable in performance. Therefore, it is easy to choose a series of compr...
Ver detalles -
Steaming system temperature control safety requirements
1136The steaming system temperature control is one of the low temperature refrigerators designed and produced by Wuxi Guanya LNEYA. The temperature range is from -5 °C to -150 °C. The secondary subcooling technology is adopted, the refrigeration is ra...
Ver detalles -
Brief introduction of explosion-proof curve heating and cooling thermostat
969The explosion-proof curve heating and cooling thermostat SUNDI series adopts compressor refrigeration and linkage heating technology, an integrated piping system, and a plate heat exchanger. It is suitable for equipment connecting reactors for ref...
Ver detalles