Working Principle and Process of Chiller Temperature Control and Pressure Controller
Air cooled chiller temperature controller is a two – position regulator, also known as chiller temperature control relay.According to the change of adjusted temperature,the chiller temperature control makes the contact on or off, thus controlling the motor or solenoid valve of the compressor.The chiller temperature controller usually uses pressure-sensitive elements to change the temperature parameters into pressure parameters to push the contact on and off.
Operating principle of chiller temperature control: the temperature wrap and bellows are filled with volatile liquid working medium.When the temperature of the temperature wrap changes, the working medium pressure changes accordingly.If the temperature of the air-cooled chiller drops, the thrust of the bellows will be reduced.Under the action of the spring force, the lever rotates counterclockwise. The two points of lever A and B will push the button of the micro switch to make the normally closed contact disconnected, thus cutting off the circuit.On the contrary, when the temperature of the air-cooled chiller rises, the thrust of the bellows increases and the lever rotates clockwise. A and B are separated from the button of the micro switch. Under the action of the spring force of the micro switch, the contact is closed and the circuit is connected.
Air cooled chiller pressure controller: the chiller pressure controller is also a two – position regulator. It is an electrical switch controlled by a pressure signal,also known as pressure relay. The pressure controller of the air cooled chiller is divided into two types: high pressure controller and low pressure controller. It can also combine the high pressure controller and low pressure controller together, which is called high and low pressure controller.
The low-pressure controller of the air-cooled chiller is used in the steam suction pipe of the compressor. When the pressure is lower than the set value, the low-pressure controller cuts off the circuit. When the pressure is higher than the set value, the circuit is connected.The low pressure controller can also be used as the energy automatic regulation of the compressor. The left side is the high pressure controller and the right side is the low pressure controller.As the compressor overpressure protection of the high pressure controller, pressure drop, can not be automatically reset.Manual reset is required to prevent the compressor from starting up again before the failure is eliminated.
Recomendaciones relacionadas
-
High temperature silicone oil cooling and heating cycle machine maintenance steps
1508The mechanical wear of the high temperature silicone oil cooling and heating cycle machine is an important factor that directly affects the refrigeration capacity. It is necessary to record the operating parameters during use, often listen to the ...
Ver detalles -
Application Of Jacketed Reactor Cooling And Heating System In Chemical Reactions
1574In the chemical industry, jacketed reactor cooling and heating devices are widely used in various chemical reactions. Application of jacketed reactor cooling and heating devices in various chemical reactions: Polymerization is a c...
Ver detalles -
Operation and maintenance of chiller cooling system for alternating high and low temperature tests
1825The operation method of the chiller cooling system for alternating high and low temperature tests: 1. Confirm whether the state of the relevant valves in the unit meets the start-up requirements. 2. Supply power to the electrical control device o...
Ver detalles -
LNEYA semiconductor refrigeration unit common fault description
2116If a high-voltage alarm occurs in the semiconductor refrigeration unit, it is necessary to check whether the external piping is blocked or dirty. Clean and remove in time. If it is an air-cooled semiconductor refrigeration device, it is necessary ...
Ver detalles
LNEYA Enfriadoras industriales Fabricante Proveedor