APLICACIONES

Dynamic constant temperature control of cold and hot sources of high-pressure reactors;

Dynamic constant temperature control of cold and hot sources of double-layer glass reactors;

Dynamic constant temperature control of cold and hot sources of double-layer reactors;

Constant temperature control of cold and hot sources of microchannel reactors;

Small constant temperature control systems, distillation system temperature control;

Low-temperature and high-temperature aging tests of materials;

Constant temperature control of combined chemical cold and hot sources;

Cooling and heating of semiconductor equipment;

Constant temperature control of refrigeration and heating of vacuum chambers.

 

 

Características del producto

 

Modelo SUNDI-320                SUNDI-320W
Rango de temperatura -30℃~180℃
Precisión a media temperatura ±0.5℃

Precisión de la temperatura del material

±1℃

Potencia calorífica 2kW
Refrigeración
capacidad
180℃ 1,5 kW
50℃ 1,5 kW
0℃ 1,5 kW
-5℃ 0.7kW
-15℃ 0.4kW
Flow、pressure max10L/min
0,8bar
Refrigerante R-404A/R507C
Tamaño de la conexión ZG1/2
Dimensión cm 35*56*75
Peso en kg 55 kg
Potencia AC 220V 50HZ 3.2kW(max)

 

 

Modelo SUNDI-135
SUNDI-135W
SUNDI-155
SUNDI-155W
SUNDI-175
SUNDI-175W
SUNDI-1A10
SUNDI-1A10W
SUNDI-1A15
SUNDI-1A15W
Rango de temperatura  -10℃~+150℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 3.5 5.5 7.5 10 15
Refrigeración
capacidad
150℃ 3.5 5.5 7.5 10 15
20℃ 3.5 5.5 7.5 10 15
-5℃ 2.1 3.3 4.2 6 9
Flow、pressure max
L/min bar
35 35 50 50 75
1 1 1.2 1.2 1.2
Compresor Highly / Panasonic / Emerson copeland / scroll compressor
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R507C
Tamaño de la conexión ZG3/4 ZG3/4 ZG1 ZG1 ZG1
Agua de refrigeración
@20℃
1300L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
1800L/H
1,5bar~4bar
ZG3/4
2400L/H
1,5bar~4bar
ZG3/4
3600L/H
1,5bar~4bar
ZG1
Dimensión cm 45*70*160 45*70*160 55*70*175 55*70*175 70*85*185
Peso en kg 165 185 235 280 300
Potencia 380V 50HZ 6.7kW 9,5 kW 12kW 15.5kW 23 kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase

 

Modelo SUNDI-235
SUNDI-235W
SUNDI-255
SUNDI-255W
SUNDI-275
SUNDI-275W
SUNDI-2A10
SUNDI-2A10W
SUNDI-2A15
SUNDI-2A15W
SUNDI-2A25
SUNDI-2A25W
SUNDI-2A38W SUNDI-2A60W SUNDI-2A95W SUNDI-2A130W SUNDI-2A200W
Rango de temperatura -25℃~+200℃(can be -25℃~+300℃)
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 3.5 5.5 7.5 10 15 25 38 60 95 130 200
Refrigeración
capacidad
200℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
100℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
50℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
20℃ 3.5 5.5 7.5 10 15 25 38 60 95 130 200
-5℃ 3 4.5 6.3 8 11 19 30 46 70 80 125
-15℃ 1.8 2.8 3.8 4.6 7 12 16 22 32 43 65
Flow、pressure  max
L/min bar
35 35 50 60 110 150 200 250 400 400 600
1.2 1.2 1.2 1.2 1.5 1.5 1.5 2.5 2.5 2.5 2.5
Compresor Tecumseh Emerson copeland / Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R507C
Tamaño de la conexión ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN50 DN65 DN65 DN80
Agua de refrigeración
@20℃
1500L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
3000L/H
1,5bar~4bar
ZG3/4
4200L/H
1,5bar~4bar
ZG3/4
5400L/H
1,5bar~4bar
DN32
10 m³/H
1,5bar~4bar
DN40
10 m³/H
1,5bar~4bar
DN40
14 m³/H
1,5bar~4bar
DN50
19m³/H
1,5bar~4bar
DN65
24m³/H
1,5bar~4bar
DN65
36m³/H
1,5bar~4bar
DN80
Dimensión cm 45*70*160 45*70*160 55*70*175 65*85*185 70*85*185 80*120*185 150*100*185 200*145*205 200*145*205 250*145*225 300*160*225
Peso en kg 165 185 230 280 300 550 750 1000 1250 1580 2150
Potencia 380V 50HZ 6.7kW 9,5 kW 15 kW 16 kW 27 kW 48 kW 55 kW 81kW 126kW 175kW 260 kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modelo SUNDI-525
SUNDI-525W
SUNDI-535
SUNDI-535W
SUNDI-555
SUNDI-555W
SUNDI-575
SUNDI-575W
SUNDI-5A10
SUNDI-5A10W
SUNDI-5A15
SUNDI-5A15W
SUNDI-4A25
SUNDI-4A25W
SUNDI-4A38W SUNDI-4A60W SUNDI-4A95W SUNDI-4A130W SUNDI-4A200W
Rango de temperatura   -45℃~+250℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
Capacidad de refrigeración 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
100℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 95 130 200
0℃ 1.8 3 5 7 10 15 25 38 60 95 130 200
-20℃ 0.85 1.5 2.3 3.6 5 7.6 11 20 29 42 54 98
-35℃ 0.25 0.45 0.9 1.5 2 3.8 4.7 9 12 18 24 43
Caudal、presión máx L/min bar 20 35 35 50 60 110 150 200 250 400 400 600
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5
Bomba de circulación Bomba de accionamiento magnético
Compresor Tecumseh/Emerson copeland/Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R507C
Tamaño de la conexión ZG1/2 ZG3/4 ZG3/4 ZG3/4 ZG1 ZG1 DN32 DN50 DN50 DN65 DN65 DN65
Agua de refrigeración
@20℃
900L/H
1,5bar~4bar
ZG1/2
1400L/H
1,5bar~4bar
ZG1/2
1800L/H
1,5bar~4bar
ZG3/4
2400L/H
1,5bar~4bar
ZG3/4
3600L/H
1,5bar~4bar
ZG1
4800L/H
1,5bar~4bar
ZG1
9 m³/H
1,5bar~4bar
DN40
10 m³/H
1,5bar~4bar
DN50
15 m³/H
1,5bar~4bar
DN50
20 m³/H
1,5bar~4bar
DN65
32 m³/H
1,5bar~4bar
DN80
46 m³/H
1,5bar~4bar
DN100
Dimensión cm 45*70*160 45*70*160 55*70*175 55*70*175 65*85*185 70*85*185 80*120*185 150*100*185 200*145*205 200*145*205 250*145*225 300*160*225
Peso en kg 160 180 195 260 320 390 620 820 1100 1350 1680 2250
Potencia 380V 50hz AC220V 4kW 7kW 9kW 13kW 16 kW 26 kW 42kW 57 kW 82 kW 136 kW 183 kW 309 kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modelo SUNDI-625
SUNDI-625W
SUNDI-635
SUNDI-635W
SUNDI-655
SUNDI-655W
SUNDI-675
SUNDI-675W
SUNDI-6A10
SUNDI-6A10W
SUNDI-6A15W SUNDI-6A25W SUNDI-6A38W SUNDI-6A60W
Rango de temperatura  -60℃~+250℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 2.5 3.5 5.5 7.5 10 15 25 38 60
Capacidad de refrigeración 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
100℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60
-40℃ 0.95 1.45 2.3 3.1 4.8 7.8 18 23 31
-55℃ 0.25 0.5 0.75 0.9 1.5 2.8 6 8 11
Flow、pressuremax  L/min bar 20 35 35 50 60 110 150 200 250
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5
Bomba de circulación Bomba de accionamiento magnético
Compresor Tecumseh/Emerson copeland/Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R23
Tamaño de la conexión ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN50
Agua de refrigeración
@20℃
1100L/H
1,5bar~4bar
ZG1/2
2000L/H
1,5bar~4bar
ZG3/4
2300L/H
1,5bar~4bar
ZG3/4
2600L/H
1,5bar~4bar
ZG3/4
3300L/H
1,5bar~4bar
ZG1
4000L/H
1,5bar~4bar
ZG1 1/4
8,5 m³/H
1,5bar~4bar
DN40
14 m³/H
1,5bar~4bar
DN50
20 m³/H
1,5bar~4bar
DN65
Dimensión cm 55*70*175 55*70*175 55*70*175 65*85*185 65*85*185 80*120*185 150*100*185 200*145*205 200*145*205
Peso en kg 205 225 300 340 380 380 980 1350 1580
Potencia 380V 50HZ 5kW 10kW 12kW 18 kW 22kW 28 kW 56kW 73 kW 110kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modelo SUNDI-825W SUNDI-835W SUNDI-855W SUNDI-875W SUNDI-8A10W SUNDI-8A15W SUNDI-8A25W SUNDI-8A38W SUNDI-8A60W SUNDI-8A80W
Rango de temperatura  -80℃~+250℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control El control de la temperatura del material y el modo de control de la temperatura de salida del equipo pueden seleccionarse libremente
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 3 3.5 5.5 7.5 10 15 25 38 60 80
Capacidad de refrigeración 250℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 80
20℃ 2.5 3.5 5.5 7.5 10 15 25 38 60 80
-60℃ 1 1.4 1.6 3 3.5 5.8 10 16 23 32
-75℃ 0.3 0.42 0.7 1.3 1.5 2.4 5 8 11 16
Flow、pressuremax
L/min bar
20 35 35 50 60 110 150 250 400 400
1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Bomba de circulación Bomba de accionamiento magnético
Compresor Emerson copeland/Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R508B
Tamaño de la conexión ZG1/2 ZG3/4 ZG3/4 ZG1 ZG1 ZG1 DN32 DN40 DN65 DN65
Agua de refrigeración
@20℃
1800L/H
1,5bar~4bar
ZG3/4
2000L/H
1,5bar~4bar
ZG3/4
2800L/H
1,5bar~4bar
ZG3/4
3500L/H
1,5bar~4bar
ZG1
4200L/H
1,5bar~4bar
ZG1
5600L/H
1,5bar~4bar
DN32
10 m³/H
1,5bar~4bar
DN40
18 m³/H
1,5bar~4bar
DN65
28 m³/H
1,5bar~4bar
DN80
30 m³/H
1,5bar~4bar
DN80
Dimensión cm 55*70*175 55*70*175 65*85*185 70*85*185 70*85*185 80*120*185 150*100*185 200*145*205 245*170*225 300*160*225
Peso en kg 240 285 345 500 600 950 1300 1550 2200 2850
Potencia 380V 50HZ 9,5 kW 11 kW 17 kW 20 kW 26 kW 36 kW 59kW 98kW 135kW 177 kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modelo SUNDI-955W SUNDI-975W SUNDI-9A10W SUNDI-9A15W SUNDI-9A25W SUNDI-9A38W SUNDI-9A60W SUNDI-9A80W
Rango de temperatura   -90℃~+250℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 5.5 7.5 10 15 25 38 60 80
Capacidad de refrigeración 250℃ 5.5 7.5 10 15 25 38 60 80
0℃ 5.5 7.5 10 15 25 38 60 80
-60℃ 2.8 3.2 4.2 6 10 16 24 32
-80℃ 0.8 1.2 1.6 2.1 3.5 6 11 15
-85℃ 0.5 0.7 0.85 1.3 1.9 3.5 6 8
Flow、pressure max
L/min bar
35 50 60 110 150 250 400 400
1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Bomba de circulación Bomba de accionamiento magnético
Compresor Emerson copeland/Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R508B
Tamaño de la conexión ZG3/4 ZG1 ZG1 ZG1 DN32 PN10 DN40 PN10 DN65 PN10 DN65 PN10
Agua de refrigeración
@20℃
3400L/H
1,5bar~4bar
ZG1
4500L/H
1,5bar~4bar
ZG1
5200L/H
1,5bar~4bar
ZG1 1/4
8 m³/H
1,5bar~4bar
DN40
12 m³/H
1,5bar~4bar
DN50
20 m³/H
1,5bar~4bar
DN65
30 m³/H
1,5bar~4bar
DN80
40 m³/H
1,5bar~4bar
DN100
Dimensión cm 80*120*185 80*120*185 80*120*185 150*100*185 200*145*205 200*145*205 250*160*225 300*160*225
Peso en kg 365 570 680 950 1400 1750 2400 3150
Potencia 380V 50HZ 16 kW 27 kW 30 kW 42kW 59kW 83kW 130 kW 188kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
OptionalPower 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

 

Modelo SUNDI-1055W SUNDI-1075W SUNDI-10A10W SUNDI-10A15W SUNDI-10A25W SUNDI-10A38W SUNDI-10A60W SUNDI-10A80W
Rango de temperatura   -100℃~+100℃
Modo de control Retroalimentación PID + Nuestro cálculo especial de control dinámico, controlador PLC
Temp control Modelo de control de temp. de proceso y temp. de camisa
Temp difference Ajustar o controlar la diferencia de temperatura entre el aceite de la camisa y el proceso de la materia prima
Editor de programas 20 programs, each program can edit 40 steps
Communication Protoco Protocolo MODBUS RTU, interfaz RS485
Material temp feedback PT100
Información sobre la temperatura The temp of 3 points: the inlet and outlet of equipment,reactor material temperature(external temp. sensor)
Precisión a media temperatura ±0.5℃
Precisión de la temperatura del material ±1℃
Potencia calorífica 5.5 7.5 10 15 25 38 60 80
Capacidad de refrigeración 100℃ 5.5 7.5 10 15 25 38 60 80
0℃ 5.5 7.5 10 15 25 38 60 80
-80℃ 2.8 3.4 4.1 5 8 13 22 30
-90℃ 1.2 1.6 2 3 4.8 7.5 12 16
 -95℃ 0.7 0.9 1.2 1.8 2.9 4.5 7.2 9.5
Flow、pressure max
L/min bar
35 50 60 110 150 250 400 400
1.2 1.2 1.5 1.5 1.5 1.5 2.5 2.5
Bomba de circulación Bomba de accionamiento magnético
Compresor Emerson copeland/Carlyle
Válvula de expansión Válvula de expansión electrónica
Evaporador Intercambiador de placas
Panel de control Pantalla táctil de 7 pulgadas, muestra la curva de temperatura, salida de datos EXCEL.
Protección de seguridad Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device,
high temperature protection and temperature fault protection.
Sistema de circulación cerrado Todo el sistema es de circulación cerrada, no hay neblina de aceite a alta temperatura y no hay vapor de agua a baja temperatura, la presión no se eleva cuando el sistema está funcionando. El sistema suministrará aceite automáticamente a baja temperatura.
Refrigerante R-404A/R23/R14
Tamaño de la conexión ZG3/4 ZG1 ZG1 DN32 DN32 DN40 DN65 DN65
Agua de refrigeración
@20℃
5000L/H
1.5~4bar
ZG1 1/4
7000L/H
1.5~4bar
DN40
9000L/H
1.5~4bar
DN40
12 m³/H
1.5~4bar
DN50
20 m³/H
1.5~4bar
DN65
25 m³/H
1.5~4bar
DN65
40 m³/H
1.5~4bar
DN80
50 m³/H
1.5~4bar
DN100
Dimensión cm 80*120*185 150*100*185 150*100*185 200*145*205 200*145*205 250*160*225 300*160*225 400*160*225
Peso en kg 565 705 890 1250 1600 2100 2950 3350
Potencia 380V 50HZ 26W 28 kW 37 kW 49 kW 69 kW 82 kW 170 kW 200 kW
Case materia Cold rolled steel powder coating (standard color 7035)
Opcional Optional Ethernet interface and computer operation software configuration
Opcional Outside touch screen display controller,
the communication line distance is 10 meter
Potencia opcional 110V 50HZ single-phase, 110V 60HZ single-phase, 230V 60HZ single-phase, 220V 60HZ 3-phase, 440V~460V 60HZ 3-phase
Opcional SUNDI series can provide optional medium temperature control accuracy of ± 0.1 ℃ and material temperature control accuracy of ± 0.1 ℃ within a heating power of 25kW

La tecnología de refrigeración de ultra alta temperatura puede enfriar directamente desde una alta temperatura de 300℃[porque sólo el medio de transferencia de calor en la cámara de expansión entra en contacto con el oxígeno en el aire (y la temperatura del tanque de expansión está entre la temperatura normal y 60℃), lo que puede reducir el riesgo de que el medio de transferencia de calor se oxide y absorba agua en el aire. A alta temperatura, ningún medio conductor de calor se evapora, y el control continuo de la temperatura de - 80℃ ~ 190℃, - 70℃ ~ 220℃, - 88℃ ~ 170℃, - 55℃ ~ 250℃ y - 30℃ ~ 300℃ se puede realizar sin presurización.

1. Muestra todos los tipos de temperaturas de control del proceso.
2. Muestra el nivel de líquido del medio conductor del calor en el vaso de expansión.
3. Indicación de funcionamiento del sistema de refrigeración.
4. Muestra la indicación de funcionamiento del calentador.
5. Muestra la indicación de funcionamiento de la bomba de circulación.
6. Muestra el control de temp. ( patrón de control de temp. de materiales, control de temp. media conductora de calor ).
7. Se puede ajustar el control del límite superior e inferior de la temperatura.
8. Se puede ajustar la diferencia de temperatura entre la camisa y el material del reactor.
9. Muestra la alarma para añadir el líquido cuando está vacío.
10. El compresor frigorífico puede funcionar de forma manual o automática.

New materials | Special gas production temperature control

API | intermediate production temp control solution

Distillation concentration temperature control solution

Más información

Más información


Desde nuestra fundación en 2006hemos atendido a más de 30.000 clientes y poseemos varias patentes que demuestran nuestra innovación y fiabilidad. Nuestros enfriadores son seleccionados por más de 100 universidad proyectos de laboratorio en todo el mundo y exportados a más de 20 países. Garantizamos la máxima calidad mediante un riguroso 3 pasos proceso de control de calidad: inspección visual, pruebas de rendimiento y pruebas de seguridad eléctrica. Nuestro compromiso con la excelencia está respaldado además por nuestro Atención al cliente 24/7 compromiso de asistencia. Además, contamos con agentes en Estados Unidos, Canadá, Australia, Rusia y Corea del Sur, lo que nos convierte en un socio global de confianza para sus necesidades de enfriadoras. Elija lneya por calidad y asistencia para su proyecto.
18+

Años de experiencia

30000+

Clientes satisfechos

25000

m² Área de producción

80+

Tecnologías patentadas

*
*
Envío....
¡Enviado con éxito!
¡Envío fallido! Vuelva a intentarlo más tarde
Error de correo electrónico.
¡Error telefónico!